Inspection Status: Correction Required
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 01/05/2000 |
ELECTRIC - RECONNECT |
|
Correction Required |
ADDTL COMMS - 1.INSTALL KO SEALS IN ALL OPEN J. BOXES AND DISCONNECTS. 2.HAVE LICENSED ELEC L-11 CONTRACTOR HAVE GENERAL REPAIR PERMIT TAKEN OUT AND DO ALL WORK. 3. NEED NEW PANEL COVERS AND PANEL SPACES. 4. REPLACE ZOO A PANEL BURNING UP BUSSING BAD AND WEATHERED 5. INSTALL GFC I OUTLETS WHRE OUTLETS ARE INWORK AREAS FOR CLASS ONE DIV TWO. 6. GROUND SERVICE TO BLDG STEEL 7. SECURE ALL CONDUITS PER CODE 8. ALL OVER CURRENT DEVICES TO BE SIZED PER ART 310 FOR CONDUCTORS 9. LOCATE OR INSTALL WATER BOND 10. REMOVE ALL EXPOSED WIRING OUTSIDE 11. CONTRACTOR TO GO THERE AFTER REPAIRS AND CERTIFY IN WRITING THAT UNIT IS SAFE TO CITY 12. ALL LIGHTING TO COMPLY WITH PIMA COUNTY CODE 7:30-8:15 JD 791-5550 EX 136 |
| 01/05/2000 |
ELECTRIC - RECONNECT |
|
Denied |
DENIED |