Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T99EL03296
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/1999 | ELECTRIC - SERVICE UPGRADE | Correction Required | ADDTL COMMS - 1. SUPPORT 1 1/4 E.M.T. PER N.E.C. (WITHIN 3 OF ELEC PANEL) 2. PVC GOING TO SHED? NOT INSTALLED AT PROPER DEPTH REMOVE OR INSTALL PER N.E.C. 3. DOUBLE LUGGING ON GROUNDING BUSHING IS NOT ALLOWED PER 110-3 N.E.C. | |
| 12/30/1999 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* |