Inspection Status: Correction Required
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 12/22/1999 |
ELECTRIC - CABLE DROP |
|
Correction Required |
ADDTL COMMS - CALL WHEN DONE NEED METAL TAGS |
| 12/21/1999 |
ELECTRIC - CABLE DROP |
|
Correction Required |
ADDTL COMMS - THE GROUNDING ELECTRODE CONDUCTOR THAT ATTACHES TO RODS IS TO CONNECT TO THE NEUTRAL THE WATER BOND CAM STAY ON THE EQUPMENT GROUND BAR FIX AND RECALL |
| 12/21/1999 |
ELECTRIC - CABLE DROP |
|
Not ready for Inspection |
IVRS - Inspection 0000* |