Permit: T99EL03258

Parcel: 11446027E

Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Permit Number - T99EL03258

Inspection Description - ELECTRIC - FINAL

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/10/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - NOT ENTERED GEN REPAIR OK EXCEPT (1 PUMP STILL INFRONT SWITCHS AND PANEL NEED 30 MIN CLEAR PER OLD CODE WHEN YOU MOVE IT WILL NEED 36 NEW CODE BOILER PEOPLE TO DO THIS BOILER PEOPLE FEFT EMT LOOSE FROM OLD BOILER LOCTION TO WALL BRACE OVER COUPLING AND AWAY FROM WALL W/IN 36 DO NOT USE TECH SCREW TO BOND FEED EQUIP GROUND FROM CONTROLLER TO PUMP ALSO NEED TO TEMP TO BOND BUSH IN CONTROLLER SAYUARO IS DONE
01/25/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. SHEET METAL SCREW IS NOT ACCEPTABLE FOR GROUNDING LUG CONNECTION USE NUT AND BOLT 2. GROUND BONDING BUSHING WHERE REDUCING WASHERS USCD 3. LABEL EQUIP AND DISCONNECT SWITCH PLEASE HAVE REPRESENT FROM SAGUARO ELEC AVAILABLE AT NEXT INSPECTION
01/25/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*