Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/28/2000 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. DISCONNECTING MEANS W/IN SIGHT REQUIRED FOR SPA 2. 90 AMP MAX BRANCH CIRCUIT ONLY 3. USE GE BREAKER |
| 01/28/2000 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 12/14/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. NEED PERMIT OR APPROVALS FOR SPA |
| 12/14/1999 |
ELECTRIC - FINAL |
|
Denied |
DENIED |
| 12/09/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - FOR SERVICE UPGRADE APPROVAL, SUBJECT TO PERMITS AND APPROVED PLAN AT JOB SITE FOR SPA AND ADDITION. |
| 12/09/1999 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |