Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/28/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. SECURE RISER PER N.E.C. USING AND APPROVED (LISTED) STRAP (2X6 IS OK) BUT ASSIST W/OTHER 2. SECURE ADDRESS LABEL TO PANEL SCREW OR RIVOT IS ACCEPTABLE 3. 40 AMP BREAKER TOO BIG FOR #10 WIRE USE 30 AMP FOR DRYER 4. INSTALL VERTICLE GFCI COVER FOR VERTICLE INSTALLATION OF J. BOX T.E.P. REQUIREMENTS ARE EXACTLY THAT HOWEVER, WE INSPECT ACCORDING THE NATIONAL ELEC, CODE ALONG WITH 99 PERCENT OF THE MUNICIPALITIES ACROSS THE U.S. |
| 12/28/1999 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |
| 12/20/1999 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/08/1999 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 12/07/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - GATE LOCKED NEED ACCESS TO ELEC SERVICE |
| 12/07/1999 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920* |