Permit: T99EL03062

Parcel: 135080670


Addresses:

7206 E SYLVANE DR

Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/28/1999 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. SECURE RISER PER N.E.C. USING AND APPROVED (LISTED) STRAP (2X6 IS OK) BUT ASSIST W/OTHER 2. SECURE ADDRESS LABEL TO PANEL SCREW OR RIVOT IS ACCEPTABLE 3. 40 AMP BREAKER TOO BIG FOR #10 WIRE USE 30 AMP FOR DRYER 4. INSTALL VERTICLE GFCI COVER FOR VERTICLE INSTALLATION OF J. BOX T.E.P. REQUIREMENTS ARE EXACTLY THAT HOWEVER, WE INSPECT ACCORDING THE NATIONAL ELEC, CODE ALONG WITH 99 PERCENT OF THE MUNICIPALITIES ACROSS THE U.S.
12/28/1999 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
12/20/1999 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
12/08/1999 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
12/07/1999 ELECTRIC - FINAL Correction Required ADDTL COMMS - GATE LOCKED NEED ACCESS TO ELEC SERVICE
12/07/1999 ELECTRIC - FINAL Denied IVRS - Inspection 0920*