Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/19/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - NO ACCESS 10:32 A.M. |
| 11/19/1999 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0920* |
| 11/16/1999 |
ELECTRIC - FINAL |
|
Correction Required |
ADDTL COMMS - 1. USE ANT: OXID PASTE ON ALL ALUM TERMINATIONS 2. ALUM COPPER SPLICE MUST UTILIZE IN APPROVED SPLICE METHOD FOR DIS-SIMILAR CONDUCTORS (AL-CU SPLIT BOLT W/SIVIDER IS ACCEPTABLE) 3. INSTALL PROPER SIZED BREAKER FOR #8 CONDUCTOR (OVEN) 4. MAKE SURE MECH PERMIT IS TAKEN OUT BY RESPONSIBLE CONTRACTOR. |
| 11/16/1999 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* |