Permit: T99EL02904

Parcel: 126191100


Addresses:

4356 E EASTLAND ST


Inspection Status: Correction Required

Inspection History: ELECTRIC - RECONNECT

Permit Number - T99EL02904

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/10/1999 ELECTRIC - RECONNECT Correction Required ADDTL COMMS - 1. 3 WIRE RECEPTACLES NOT ALLOWED ON NON GROUNDING CIRCUIT UNLESS GFCI PROTECTED 2. INSTALL SMOKE DETECTOR IN HALL CEILING 3. PROPERLY WIRE FLOOR FIXTURES ABOVE KITCHEN SINK AREA 4. JUNCTION EXPOSED WIRES AT SINK LOCATION 5. INSTALL MISSING COVER AT J-BOX (CEILING) AT SOUTH EAST BEDROOM 6. PROPERLY WIRE KITCHEN CEILING FIXTURE 7. INSTALL MISSING RECEPTACLE SOUTH WEST ROOM 8. JUNCTION OPEN SPLICE IN WORKSHOP (ABOVE THE LIGHT SWITCH) 9. ATTACH LOOSE J-BOX (S.W. CORNER OF HOUSE OUTDOORS) 10. REMOVE U.F. WIRE AT EAST GATE OR WIRE PER CODE 11. NEED PERMITS FOR NEW WATER HEATER AND FURNACE
11/10/1999 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*