Inspection Status: Correction Required
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 12/22/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - 1. INSTALL JUMPER AT #2 TO SERVICE AROUND CONDUIT 2. INSTALL GROUNDING ELECTRODE SYSTEM AT ALL 2ND BLDGS AND WATER BONDS 3. ADDRESS PANELS AT METERS 1,2,3 4. RECALL IN WHEN READY 5. INSTALL GROUNDING BUSHING OR LOCKNUTS AND BUSHING AT RISER |
| 12/22/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |
| 11/24/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - NO ONE HOME 10 AM ELECT INSPECTOR HERE TO CHECK SERVICE UPGRADE DOG IN YARD PLS RECALL AND LEAVE INSTRUCTIONS 1 1/2 PVC TO MAIN OK 1 1/4 TO RENTAL (OK TO COVER LEAVE ENDS OPEN) 1 TO STUDIO APT |
| 11/24/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
OK UNDG FEEDS TO EACH-- |
| 11/24/1999 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
OF 3 SERVICES |