Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T99EL01853
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2000 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | 1. DOUBLE LUGGING NOT ACCEPTABLE ON GROUNDING CONNECTION AT PANEL B ALSO 2. SHEET METAL SCREW IS NOT ACCEPTABLE FOR GROUNDING LUG ATTACHMENT 3. CIR 38 PERF. ARTS PANEL IS IMPROPERLY GROUNDED INSTALL A PROPER GROUNDING LUG BUS BAR ETC. NO DOUBLE LUGGING |