Permit: T99EL01853


Addresses:

200 S ALVERNON WY


Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T99EL01853

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
07/31/2000 ELECTRIC - INTERMEDIATE Not ready for Inspection 1. DOUBLE LUGGING NOT ACCEPTABLE ON GROUNDING CONNECTION AT PANEL B ALSO
2. SHEET METAL SCREW IS NOT ACCEPTABLE FOR GROUNDING LUG ATTACHMENT
3. CIR 38 PERF. ARTS PANEL IS IMPROPERLY GROUNDED INSTALL A PROPER GROUNDING LUG BUS BAR ETC. NO DOUBLE LUGGING