Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - RECONNECT
Permit Number - T99EL00410
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2000 | ELECTRIC - RECONNECT | Correction Required | ADDTL COMMS - 1. SEAL HOLE ON TOP OF ELECT BOX 2. GROUND PANEL ENCLOSURE TO GROUND BAR 3. INSTALL 15 AMP BREAKER WHERE 30 AMP BREAKER INSTALLED 4. INSTALL ROMEX CONNECTOR WHERE WIRE ENTERS SIDE 5. GROUND WIRE ENTERS SIDE 6. CLAMP FOR LIFE LINE NOT SCREWED 7. INSTALL 15 AMP CIRCUIT BREAKERS FOR ALL #14 WIRE 8. SO CORD FEEDING COOLER DISCONNECT HAS TO BE IN CONDUIT 9. USE A BUSHING WHERE MOBILE HOME CORD PASSES THUR METAL FLASHING 10 USE STRANDED WIRE CONNECTORS FOR WIRES IN COOLER BOX | |
02/15/2000 | ELECTRIC - RECONNECT | Denied | DENIED | |
03/18/1999 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999* | |
03/03/1999 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0333* |