Permit: T99EL00410

Parcel: 10709064B


Addresses:

2444 N 14TH AV #47


Inspection Status: Correction Required

Inspection History: ELECTRIC - RECONNECT

Permit Number - T99EL00410

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/15/2000 ELECTRIC - RECONNECT Correction Required ADDTL COMMS - 1. SEAL HOLE ON TOP OF ELECT BOX 2. GROUND PANEL ENCLOSURE TO GROUND BAR 3. INSTALL 15 AMP BREAKER WHERE 30 AMP BREAKER INSTALLED 4. INSTALL ROMEX CONNECTOR WHERE WIRE ENTERS SIDE 5. GROUND WIRE ENTERS SIDE 6. CLAMP FOR LIFE LINE NOT SCREWED 7. INSTALL 15 AMP CIRCUIT BREAKERS FOR ALL #14 WIRE 8. SO CORD FEEDING COOLER DISCONNECT HAS TO BE IN CONDUIT 9. USE A BUSHING WHERE MOBILE HOME CORD PASSES THUR METAL FLASHING 10 USE STRANDED WIRE CONNECTORS FOR WIRES IN COOLER BOX
02/15/2000 ELECTRIC - RECONNECT Denied DENIED
03/18/1999 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*
03/03/1999 ELECTRIC - RECONNECT Denied IVRS - Inspection 0333*