Permit: T99CM05982

Parcel: 12308039A


Addresses:

2829 E SPEEDWAY BL

Inspection Status: Correction Required

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
03/10/2000 PLUMBING - ABOVE CEILING Correction Required ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. GAS PRESSURE TEST OK 4. ALL CORRECTIONS HAVE BEEN MADE 5. OK TO DRYWALL 6. NOTE: GREASE TRAP NOT INSTALLED AT THIS TIME
03/10/2000 PLUMBING - ABOVE CEILING Correction Required ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. GAS PRESSURE TEST OK 4. ALL CORRECTIONS HAVE BEEN MADE 5. OK TO DRYWALL 6. NOTE: GREASE TRAP NOT INSTALLED AT THIS TIME
03/09/2000 PLUMBING - ABOVE CEILING Not ready for Inspection NOT READY FOR INSPECTION
03/07/2000 PLUMBING - ABOVE CEILING Correction Required ADDTL COMMS - 1. GAS PRESSURE TEST WAS DOWN TO ZERO LBS 2. GAS LINE MUST BE AT LEAST 6 A.F.F. SEE SECTION 1211.3 UPC. 3. 2 GAS LINE MUST BE SUPPORTED EVERY 10 4. ALL ABS HORIZONTAL VENTS MUST BE HUNG OR STRAPED EVERY 4. 5. NO WATER TEST ON WASTE SYSTEM 6. NO CLOSET RINGS INSTALLED 7. NO P&T DRAIN FOR WATER HTR INSTALLED 8. LOTS OF LOOSE COPPER WATER LINES ON HORIZONTAL AND VERTICAL DROPS 9. GREASE TRAP NOT INSTALLED AT THIS TIME.
03/07/2000 PLUMBING - ABOVE CEILING Denied IVRS - Inspection 0000*