Inspection Status: Correction Required
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/10/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. GAS PRESSURE TEST OK 4. ALL CORRECTIONS HAVE BEEN MADE 5. OK TO DRYWALL 6. NOTE: GREASE TRAP NOT INSTALLED A THIS TIME |
| 03/10/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. GAS PRESSURE TEST OK 4. ALL CORRECTIONS HAVE BEEN MADE 5. OK TO DRYWALL 6. NOTE: GREASE TRAP NOT INSTALLED A THIS TIME |
| 03/09/2000 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |
| 03/07/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. GAS PRESSURE TEST WAS DOWN TO ZERO LBS 2. GAS LINE MUST BE AT LEAST 6 A.F.F. SEE SECTION 1211.3 UPC. 3. 2 GAS LINE MUST BE SUPPORTED EVERY 10 4. ALL ABS HORIZONTAL VENTS MUST BE HUNG OR STRAPED EVERY 4 5. NO WATER TEST ON WASTE SYSTEM 6. NO CLOSET RINGS INSTALLED 7. NO P&T DRAIN FOR WATER HTR INSTALLED 8. LOTS OF LOOSE COPPER WATER LINES ON HORIZONTAL AND VERTICAL DROPS. 9. GREASE TRAP NOT INSTALLED AT THIS TIME. |
| 03/07/2000 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0000* |