Inspection Status: Correction Required
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 04/10/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. ALL CORRECTIONS HAVE BEEN MADE 4. OK TO DRYWALL |
| 04/03/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. 2 HORIZONTAL RE VENT EXCEEDS MAX. LENGTH. 2. A.W. STAND PIPE CAN ONLY BE MAX 30 18-MIN 3. A.W. P-TRAP MUST BE MIN 6 TO BOTTOM OF WEIR A.F.F. 4. WILL REQUIRE REVISED AND APPROVED DRAWING ON WASTE AND VENT SYSTEM PRIOR TO FINAL. |
| 04/03/2000 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0000* |