Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
03/23/2001 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
03/20/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/STOPPED INSPECTION INSTALL ALL FRAMING PER PLAN. A35, H2.5'S MISSING HDGA MISSING REAR FILL ALL NAIL HOLES PA ANCHORS. FILL IN I JOISTS SOLIDLY AT BEARING INSTALL GREEN PLATES WHERE APPLICABLE EXTERIOR FRAME COLUMNS TO BE MIN. 4" ABOVE CONCRETE.
02/28/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. A35'S LEDGER TO STUDS, MISSING HOLD DOWNS. 2. GREEN BOTTOM PLATES PORCH PIERS. 3. POSITIVE CONNECTION ALL BEAMS LODGERS POSTS ETC. 4. DBL AND TRIPLE TRIMMERS WHERE APPLICABLE.
02/12/2001 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/1. MISSING HURRICANE CLIPS (N-35) ON S.E. EYEBROWS. 2. MISSING STUD CLIPS TOP, N.W. CORNER. 3. STUD CLIPS ON EAST POOL WALL MISSING. 4. ALTERNATE HOLDOWN NEEDED AT S.W. SLIDER. 5. SHIM HEADERS WHERE NEEDED MANY ROOF AND WALL PANELS GOT NAILED OFF AT INSPECTION. 6. INSTALL PLY AND 3 CREW OFF WALK DECK ABOVE POOL.