Permit: T99CM05973

Parcel: 119032870


Addresses:

732 W 42ND ST

Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/17/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. UNABLE TO TEST WIRING CHANGES AND OUTLETS. WILL TEST WHEN THE POWER IS ON. 2. GAS LINE HAS BEEN EXTENDED TO THE HEATER. REQUIRES NEW GAS PRESSURE TEST. MINIMUM OF 10 PSI. 3. HEATER REQUIRES GAS SHUT-OFF VALVE BEFORE FLEX LINE. 4. BEDROOM AND LIVING ROOM REQUIRE BATTERY OPERATED SMOKE DETECTORS. 5. MANY OUTLETS WIRED INCORRECTLY. 6. LABEL ALL CIRCUITS IN ELECTRIC PANEL.
02/17/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
01/21/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. A LAUNDRY RISER AND S TRAP HAVE BEEN ADDED TO BATHROOM CLEAN OUT. 2. BATHROOM ELECTRIC OUTLET WIRED INCORRECTLY. 3. BEDROOM ELECTRIC OUTLET HAS OPEN GROUND. 4. KITCHEN HAS NO USABLE SINK. 5. HOUSE HAS NO HEAT. 6. KITCHEN ELECTRIC OUTLET HAS OPEN GROUND. REFER TO MINIMUM HOUSING.
01/21/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
01/19/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. OPEN A 2 ABS CONNECTION IN BACK ROOM REQUIRES CAP. 2. WATER HEATER GAS VALVE AND FLEX LINE MUST BE CONNECTED. NOTE: NEXT INSPECTION CALL FOR 02090 AND 03090 INSPECTIONS AFTER POWER IS ON.
01/19/2000 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
01/04/2000 ELECTRIC - FINAL Not ready for Inspection NOT READY FOR INSPECTION
12/29/1999 ELECTRIC - FINAL Denied IVRS - Inspection 0999*