Permit: T99CM05967

Parcel: 122050630


Addresses:

4320 E EDISON ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/17/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/16/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
OWNER OCCUPANT DOING WORK
SERVICE OK USED EXISTING ALL IN ONE,
FANS NOT MOUNTED OR INSTALLED YET
11/14/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
SUB PANEL REQUIRES SEPARATION OF NEUTRAL AND GROUND
REMOVE A/C FEEDER WIRES FROM SUB PANEL. SUB PANEL CANNOT BE USED TO FEED THRU
ADD GROUND BAR IN SUB PANEL
ADD GROUND WIRE FROM MAIN PANEL TO SUB PANEL GRD BAR