Inspection History: MECHANICAL - PROGRESS

Date Description Inspector Results Comments
01/02/2001 MECHANICAL - PROGRESS Approved IVRS - Inspection 0000*
11/28/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
USE BREAK AWAY JOINTS AT FIRE DAMPERS
INSTALL FIRE RATED ACCESS DOORS
LINE ENTIRE OPENING ON FIRE DAMPER IN NORTH CORRIDOR 1ST FLOOR
NEED TO SEE THE REST OF OPENINGS BEFORE INSTALLING FIRE DAMPERS
FIRE TAPE DAMPER OPENINGS