Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - PROGRESS
Permit Number - T99CM05958
Inspection Description - MECHANICAL - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/02/2001 | MECHANICAL - PROGRESS | Approved | IVRS - Inspection 0000* | |
11/28/2000 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection 0000* USE BREAK AWAY JOINTS AT FIRE DAMPERS INSTALL FIRE RATED ACCESS DOORS LINE ENTIRE OPENING ON FIRE DAMPER IN NORTH CORRIDOR 1ST FLOOR NEED TO SEE THE REST OF OPENINGS BEFORE INSTALLING FIRE DAMPERS FIRE TAPE DAMPER OPENINGS |