Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T99CM05958

Parcel: 128100760


Addresses:

350 S WILLIAMS BL


Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Permit Number - T99CM05958

Inspection Description - MECHANICAL - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
01/02/2001 MECHANICAL - PROGRESS Approved IVRS - Inspection 0000*
11/28/2000 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection 0000*
USE BREAK AWAY JOINTS AT FIRE DAMPERS
INSTALL FIRE RATED ACCESS DOORS
LINE ENTIRE OPENING ON FIRE DAMPER IN NORTH CORRIDOR 1ST FLOOR
NEED TO SEE THE REST OF OPENINGS BEFORE INSTALLING FIRE DAMPERS
FIRE TAPE DAMPER OPENINGS