Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T99CM05893
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/10/2001 | FRAMING | Approved | IVRS - Inspection 0000* | |
08/16/2000 | FRAMING | Partial Approval | IVRS - Inspection 0000*/1`. COMPLETE FIRE PLACE FLUE THROUGH ROOF 2. REPLACE HOLDOWN AT RADIUS. | |
08/15/2000 | FRAMING | Partial Approval | IVRS - Inspection 0000*/1. PROVIDE WEB STIFFNERS AS PER CALC'S STRAP ALL POST TO BEAM CONNECTIONS BEFORE FINALS PROVIDE REVISION FOR BEAMS NOT SHOWN ON PLANS. 2. GROUND ALL METAL BOXES. 3. PROVIDE 1 INCH CLEARANCE FROM COMBUSTIBLE AT ALL TYPE B FLUE VENTS. | |
08/14/2000 | FRAMING | Denied | IVRS - Inspection 0999*/1. ALL DOCUMENT MUST HAVE CITY APPROVED STAMP. 2. F/P NOT COMPLETE NEED TO CALL FOR INSP WHEN ALL WORK IS COMPLETED. | |
08/09/2000 | FRAMING | Not ready for Inspection | 1. WEB STIFFENERS MISSING THRU OUT. 2. STRAP ALL BEAMS TO POSTS AND WALLS. 3. CHASE MISSING AT FUR VENT. HAVE ARCHET. CHECK SITE PRIOR TO RE INSPECTION |