Permit: T99CM05859

Parcel: 13109144C


Addresses:

5750 E 28TH ST

Inspection Status: Correction Required

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/08/2000 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - CHECK W/REGISTRAR VALVE ELEC CARLOS CANYZ
02/03/2000 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
02/01/2000 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - NEED L-11 LIC CONTRACTOR TO FINISH JOB
02/01/2000 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection 0000*
01/31/2000 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. GROUND ALL METAL BOXES PER ART. 250 N.E.C. (ATTIC) 2. REMOVE ALL UNUSED N.M. CONNECTORS AND SEAL UNUSED OPENINGS 110-124 & 373-4 3. PER ART 300-14 LEAVE AT LEAST 6 OF CONDUCTOR. REWORK REPULL CABLE TO ACHIEVE THIS MIN REQUIREMENT OF ART 300-14 NATIONAL ELEC, CODE 4. FIRE CAULK ALL FIRE WALL PENETRATIONS AND SLEEVE PER N.E.C. FINISH BOX MAKE UP OF EQUIP GROUNDING CONDUTORS AND NEUTRALS (GROUNDING CONDUCTORS) PRIOR TO INSPECTION
01/31/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999$