Inspection Status: Correction Required
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/27/2000 |
ELECTRIC - ABOVE CEILING |
|
Correction Required |
ADDTL COMMS - NOTE DO NOT TILE 1. J-BOXES OVERFILLED 2. CONDUIT NOT SECURED PER N.E.C. 3. FIXTURES MISSING SIESMIC WIRES 4. FIXTURE WHIP DAMAGE AT J-BOX ENTRY NOTE DO NOT TILE. |
| 03/27/2000 |
ELECTRIC - ABOVE CEILING |
|
Denied |
DO NOT TILE |
| 03/22/2000 |
ELECTRIC - ABOVE CEILING |
|
Correction Required |
ADDTL COMMS - ALL RELOCATED OR NEW INSTALLATION FIXTURES TO HAVE SEMIC TIES. |
| 03/22/2000 |
ELECTRIC - ABOVE CEILING |
|
Denied |
DENIED |