Permit: T99CM05746

Parcel: 13815018E

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/14/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/08/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/1. GROUND ALL METAL ELECTRIC BOXES. 2. MAKE UP ALL GROUNDS IN ELECTRIC BOXES AND SECURE WITH MECHANICAL FASTENERS. 3. N.M.C. ELECTRIC CABLE NOT ALLOWED TO BE EDGE NAILED MANY STAPLES FOR ELECTRIC WIRES. TOO TIGHT. 4. GAS AND ELECTRIC PIPES MUST BE ELECTRICALLY BONDED. 5. PROTECT ELECTRIC WIRES AT FAN BOX K/O'S.