Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/14/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 03/08/2001 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/1. DOUBLE 2 X 6 HEADERS WITH TRIMMERS REQUIRED AT ALL WINDOWS AND DOOR ON WEST WALL. 2. HOLD DOWNS MUST BE ATTACHED TO FULL LENGTH DOUBLE STUDS. 3. BLOCK FURNACE PLATFORM BETWEEN ALL WALL STUDS. 4. ANCHOR BOLTS REQUIRED WITHIN 12" OF ALL SILL PLATE CUTS ON FRAME WALLS. 5. NO ATTIC ACCESS. 6. ANCHOR BOLTS MISSING MANY AREAS 1/3 AND WITHIN 12" OF ENDS AND SPLICES. |