Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/05/2000 |
FRAMING |
|
Correction Required |
ADDTL COMMS - APPROVED - THANK YOU FOR MARKING YOUR LOTS. |
| 04/03/2000 |
FRAMING |
|
Correction Required |
ADDTL COMMS - DENIED - 1. THE COMMON WALL MUST BE FIRE STOPPED WITH 5/8 GDW ON OSB UNDER WATER HEATER PLATFORM. 2. LTT HOLD-DOWNS REQUIRED AT GARAGE COMMON WALL. 3. SHEARWALLS ARE NOT BLOCKED PER 40 OF D1. 4. NAILS TO BLOCKS AND TOP PLATES S/B REMOVED PER 40 OF D1. 5. EQUALIZING GRILL FRAMES ABOVE DOORS MUST BE BLOCKED ON 3 SIDES. 6. RETURN AIR GRILLS MUST BE BLOCKED ON 3 SIDES. 7. DRYER EXHAUST TUBE MUST BE STRAPPED NEAR ROOF JACK. 8. PROVIDE A SET OF PLANS FOR EACH SITE. IT IS NOT INCUMBENT UPON THE INSPECTOR TO CHASE DOWN AND MATCH PLANS TO EACH SITE. |
| 04/03/2000 |
FRAMING |
|
Denied |
IVRS - Inspection 0950* |