Inspection Status: Correction Required
Inspection History: OUTDOOR LIGHTING FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/31/2000 |
OUTDOOR LIGHTING FINAL |
|
Correction Required |
ADDTL COMMS - 1. IDENITY UNDERGROUND CONDUTOR AT ALL ACCESSABLE LOCATINS HAND HOLE, ALL BOXES, CONTROLER, CONTROL CABINET, ETC CITY ORDINANCE #9287 210-510 2. 250-8 CAN NOT USE SHEET METAL SCREWS TO ATTACH LUGS NEED BOLT ALSO 250-12 CLEAN SURFACE. 3. SUPPORT CONDUTROS IN CONTROL CABINET 4. SUPORT FEEDER CONDUCTORS 370-17 5. USE CORRECT CONDUTRO SIZED TO MATCH OVER CORRECT DEVICE 6. PANEL A BREAKERS NOT AS PLANS. PLEASE CORRECT OR PROVIDED REVISED DRAWINGS FROM ENGINEER 7. NEED CORRECT SIZE BONDING CONDUTOR PER CALBE 250-122 AT SERVICE PANEL |
| 05/31/2000 |
OUTDOOR LIGHTING FINAL |
|
Denied |
IVRS - Inspection 0999* |
| 04/13/2000 |
OUTDOOR LIGHTING FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |