Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T99CM05432
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
07/16/2001 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
07/10/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0950*1.) TELEPHONE ROOM INCOMPLETE 2.) FIRE ALARM SYS. 3.) SUB PANEL NEED INDEX. | |
06/21/2001 | ELECTRIC - FINAL | Not ready for Inspection | NOT READY 1.) NEED WATER BOND TO MAIN SERVICE 2.) REMOVE GRD TO NEUTRAL LINK AT DSB SWITCH GEAR 3.) FINISH FAN COILS 4.) TERMINATE FIRE ALARM CONTROLS 5.) FINISH ALL OTHER ELECTRICAL 6.) INSTALL ALL PANEL COVERS. | |
10/06/2000 | ELECTRIC - FINAL | Partial Approval | OK TEMP POWER AND FEEDERS AND GROUNDING OF CONSTRUCTION TRAILER OK ELECT FINAL TEMP WIRING PER 99 NATIONAL ELEC CODE 305.1 |