Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 01/24/2001 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 01/23/2001 |
FRAMING |
|
Partial Approval |
IVRS - Inspection 0000*/OK TO INSULATE AND DRYWALL ALL BUT KITCHEN BATH AND MECH ROOM. 1. NAIL PROTECT ALL PLUMBING AND ELECTRIC IN MECH ROOM AND BATH. 2. LOW PRESSURE ON GAS TEST. 3. BOND GAS LINE. 4. ELECT WIRES OUTSIDE OF WALL CAVITY IN BATH AND MECH ROOM. 5. SHOWER MUST HAVE TEMP/PRESSURE BALANCE VALUE OR APPROVED ALTERNATIVE. 6. K. COUNTER OUTLETS REQUIRED WITHIN 12" OF COUNTER TOP AND WITHIN 24" OF EITHER SIDE OF SINK AND 48" THERE AFTER AND ON 2 SEPARATE CIRCUITS. |
| 05/23/2000 |
FRAMING |
|
Not ready for Inspection |
NOT READY FOR INSPECTION |