Permit: T99CM05274

Parcel: 115173680

Inspection Status: Correction Required

Inspection History: FRAMING

Permit Number - T99CM05274

Inspection Description - FRAMING

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/11/2000 FRAMING Correction Required ADDTL COMMS - O.K. TO ROCK INSIDE OF HOUSE. CARPORT LID REMAIN OFF UNITL TO3 TRUSSES ARE RESOLVED.
01/11/2000 FRAMING Partial Approval IVRS - Inspection 0000*
01/04/2000 FRAMING Correction Required ADDTL COMMS - TRUSS CALCS ARE NOT APPROVED, CALCS MISSING ANCHOR BOLTS AT ALL SHEARWALLS (SWI).
01/04/2000 FRAMING Denied IVRS - Inspection 0999*
12/29/1999 FRAMING Correction Required ADDTL COMMS - TRUSS CALCS PROVIDED ASRE NOT APPROVED BY COT OR OTHER REPRESENTATIVE AGENCY. PROVIDE LAYOUT SHEET FOR TRUSSES. NO TRUSS CALCS FOR TRUSSES AT ENTRY. TRUSS TO3 NOT INSTALLED AT THIS HOUSE. POSITION #12 & #7 MISSING AT INSTALLED TRUSSES. ALSO, POSITION #12 IN UNCLEAR AS TO BEARING POINT. TRUSS TO3A INDICATES 3 POINT BEARING?
12/29/1999 FRAMING Denied IVRS - Inspection 0999*
12/21/1999 FRAMING Correction Required ADDTL COMMS - 8. NO APPROVED TRUSS CALCS. 9. PROVIDE X BRACING AT 25-0 O.C. (OR MID SPAN) NOTE: PROVIDE ADDRESS AND LOT #S AT EACH SITE.
12/21/1999 FRAMING Denied IVRS - Inspection 0999*