Inspection Status: Correction Required
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/06/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. RAIN LEADER WATER TEST OK 4. ALL CORRECTIONS HAVE BEEN MADE 5. OK TO DRYWALL 6. NOTE: CLOSET RINGS HAVE NOT BEEN SET AT THIS TIME |
| 03/02/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. MUST HAVE APPROVED HANGERS FOR HORIZONTAL VENT EVERY 4 WOOD IS NOT A APPROVED HANGER. 2. LAVATORY FOR MENS RESTROOM DIETY ARM IS 2 TRAP ARM AT 2 TRAP MUST SIZE AS DRAIN SERVED 3. RAIN LEADERS WATER TEST OK 4. SOIL WATER TEST FOR SINK IN BREAK RM OK 5. OK TO BACKFILL TRENCH 6. MUST USE SPECIALTY COUPLINGS ON ABS FOR VERTICAL RAIN LEADERS |
| 03/02/2000 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0000* |