Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/21/2000 |
PLUMBING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1. INADEQUATE HIGH LOW COMBUSTION AIR FOR WATER HEATER. REQUIRES 100 SQ. IN HIGH AND LOW. PRESENTLY APPROX. 40" HIGH LOW EACH. 2. PROVIDE CITY APPROVED PLAN FOR GAS AND ELECTRIC WORK DONE. 3. NOTE: WASTE VENT AND WATER HEATER VENTS WITHIN 10 FEET OF EVAP. COOLER WILL HAVE TO TERMINATE 1 FOOT ABOVE EVAP. COOLER. ELECTRIC INSTALLATION IS AS PER DELETED PLAN ALTHOUGH MUCH NEW WORK. GAS PIPE SIZE IS PER CODE AND TESTS GOOD APPROX 10 LF OF CORRIGATED 3/4 GAS LINE INSTALLED OK TO INSULATE AND DRYWALL. |
| 04/21/2000 |
PLUMBING - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* |