Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T99CM05194
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2001 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* NEED TO SEE WATER TEST TO 42" ON DWV |
|
01/31/2001 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000* ALL CORRECTIONS MADE OK OK TO COVER |
|
01/16/2001 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
01/12/2001 | PLUMBING - INTERMEDIATE | Denied | HORIZONTAL ABS MUST BE SUPPORTED MAX 4 1/2' (WITH APPROVED STRAP) HORIZONTAL COPPER MUST BE SUPPORTED MAX 6" TABLE 3-1 905.1 GRADE OF VENTS 905.3 HORIZONTAL VENTING 707.10 CLEAN-OUT CLEARANCES NEED TO SEE WATER TEST TO 42" ON DWV NEED TO SEE PRESSURE TEST ON COPPER DON'T FORGET T&P RELIEF DRAINS NEED TO SEE CLOSET RINGS |