Inspection History Details
Inspection Status: Correction Required
Inspection History: PLUMBING - ABOVE CEILING
Permit Number - T99CM05003
Inspection Description - PLUMBING - ABOVE CEILING
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/29/2000 | PLUMBING - ABOVE CEILING | Correction Required | ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUITON OK 3.OK TO DRYWALL | |
| 02/16/2000 | PLUMBING - ABOVE CEILING | Correction Required | ADDTL COMMS - 1. ROUGH PLUMBING NOT TO PLAN AND SPECS 2. SPECS CALL FOR CAST IRON NO HUB 3. 2 DIRTY ARMS EXCEEDS 135 DEGREES A CLEAN OUT IS REQUIRED WHEN WASTE LINE EXCEEDS 135 DEGREES BUT CANNOT BE ON DIRTY ARM 4. NO ROUGH PLDG FOR P-3? 5. OVERHEAD WATER DISTRIBUTION NOT TO PLAN | |
| 02/16/2000 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection 0000* |