Permit: T99CM05003

Parcel: 127035430


Addresses:

5639 E 5TH ST #B


Inspection Status: Correction Required

Inspection History: PLUMBING - ABOVE CEILING

Permit Number - T99CM05003

Inspection Description - PLUMBING - ABOVE CEILING

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/29/2000 PLUMBING - ABOVE CEILING Correction Required ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUITON OK 3.OK TO DRYWALL
02/16/2000 PLUMBING - ABOVE CEILING Correction Required ADDTL COMMS - 1. ROUGH PLUMBING NOT TO PLAN AND SPECS 2. SPECS CALL FOR CAST IRON NO HUB 3. 2 DIRTY ARMS EXCEEDS 135 DEGREES A CLEAN OUT IS REQUIRED WHEN WASTE LINE EXCEEDS 135 DEGREES BUT CANNOT BE ON DIRTY ARM 4. NO ROUGH PLDG FOR P-3? 5. OVERHEAD WATER DISTRIBUTION NOT TO PLAN
02/16/2000 PLUMBING - ABOVE CEILING Denied IVRS - Inspection 0000*