Inspection Status: Correction Required
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 01/10/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. GROUND WIRES CAN NOT BE CONNECTED TO NEUTRAL ON SUB PANEL. 2. SUB PANEL MUST HAVE A GROUND SYSTEM-INSTALL 2 GROUND RODS 6 FEET APART CONNECTED TO PANEL WITH CONTINUOUS #4 WIRE. PROVIDE ELECTRIC CONTRACTOR NAME, LIC # AND PHONE-# BY NEXT INSPECTION. |
| 01/10/2000 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 01/07/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. ELECTRIC SUB PANEL MUST HAVE A BONDED NEUTRAL BAR FOR ALL GROUND WIRES AND ALL NEATRUAL WIRES MUST BE ATTACHED TO AN ISOLATED NEUTRAL BAR. 2. ALL GROUNDS IN ELECTRIC BOXES MUST BE FASTENED TOGETHER (TWISTED) AND SECURED WITH AN APPROVED MECHANICAL FASTNER. 3. 2X4 BOX BY DOOR OVER LOADED. USE LARGER BOX-TOO MANY WIRES. 5. ADDED CIRCUITS-REVISE PLAN TO AS BUILT AND HAVE APPROVED BY CITY OF TUCSON OR BUILD TO PLAN. NOTE: YOU MUST HAVE CITY APPROVED PLAN ON SITE STOPPED INSPECTION. |
| 01/07/2000 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 12/29/1999 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |
| 12/20/1999 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. ELECTRIC NOT COMPLETE. |
| 12/20/1999 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999* |