Permit: T99CM04985

Parcel: 13316025E


Addresses:

2200 N WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
09/23/2001 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK LETTERING UP CONTRACTOR WILL PLACE CAUTION TAPE ON TOP OF LINE.
09/20/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) LETTERING NOT TURNED UP SAVE APPROVED DRAWING AND LISTING FOR PIPE UNTIL READY FOR INSPECTION
09/19/2001 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection 0000*1.) NOT READY FOR INSPECTIONS.
09/18/2001 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection 0999*1.) 2" PE GAS YARDPIPING TO GENERATOR TO BE SDR-11 TURN PIPING SO LETTERING IS UP 2.) NOT INSTALLED PER PLAN. ARCHETECT SPEC'D BLACK IRON PIPE W/SCOTCH COAT. REVISE PLAN AND CALL FOR INSPECTION.