Permit: T99CM04895

Parcel: 129020510


Addresses:

18 S EASTBOURNE AV


Inspection Status: Correction Required

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T99CM04895

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/19/2000 ELECTRIC - ABOVE CEILING Correction Required ADDTL COMMS - 1. J-BOX OVERFILLED 2. GROUND J-BOX PER N.E.C. 3. SECURE FLEX PER N.E.C. 4. INSTALL FHA PLATES PER N.E.C. 5. INSTALL PROPER SPLICE OF GROUNDING 6. DE RATE CONDUCTORS PER 310-16 FOR COMBINED HOME RUNS 7. MAKE PROPER TRANSITION INTO ELEC PANEL FROM PANEL FEEDER 8. NEED NAME OF LIC ELECTRICAL CONTRACTOR DOING THIS WORK 791-5550 X 136