Inspection Status: Correction Required
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T99CM04895
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/19/2000 | ELECTRIC - ABOVE CEILING | Correction Required | ADDTL COMMS - 1. J-BOX OVERFILLED 2. GROUND J-BOX PER N.E.C. 3. SECURE FLEX PER N.E.C. 4. INSTALL FHA PLATES PER N.E.C. 5. INSTALL PROPER SPLICE OF GROUNDING 6. DE RATE CONDUCTORS PER 310-16 FOR COMBINED HOME RUNS 7. MAKE PROPER TRANSITION INTO ELEC PANEL FROM PANEL FEEDER 8. NEED NAME OF LIC ELECTRICAL CONTRACTOR DOING THIS WORK 791-5550 X 136 |