Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/23/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000* | |
| 03/20/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* 1) LIGHT SWITCHES MUST BE GROUNDING TYPE 380-9 NEC 2) PUSH IN PLASTIC BUSHINGS NOT APPROVED FOR ROMEX TERMINATION UNLESS CLAMP TYPE 370-17 NEC 3) BOXES FOR FANS MUST BE APPROVED FOR USE 4) CHECK 370-16A NEC. FOR CONDUCTOR FILL IN DEVICE BOXES, EACH DEVICE COUNTS AS 1-CONDUCTOR, 2 AND 4 GANG BOXES APPEAR TO BE OVER FILLED |