Permit: T99CM04892

Parcel: 12102005B


Addresses:

5425 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/23/2001 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
03/20/2001 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245* 1) LIGHT SWITCHES MUST BE GROUNDING TYPE 380-9 NEC 2) PUSH IN PLASTIC BUSHINGS NOT APPROVED FOR ROMEX TERMINATION UNLESS CLAMP TYPE 370-17 NEC
3) BOXES FOR FANS MUST BE APPROVED FOR USE
4) CHECK 370-16A NEC. FOR CONDUCTOR FILL IN DEVICE BOXES, EACH DEVICE COUNTS AS 1-CONDUCTOR, 2 AND 4 GANG BOXES APPEAR TO BE OVER FILLED