Inspection Status: Correction Required
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2000 |
FRAMING |
|
Correction Required |
ADDTL COMMS - APPROVED - CHECK SIZE OF FURNACE AT FINAL FOR PROPER COMBUSTION AND RELIEF. |
| 03/24/2000 |
FRAMING |
|
Correction Required |
ADDTL COMMS - NOT READY - 1. COMBUSTION RELIEF DUCT REQUIRES 100 SQ.IN. EACH. 2. CHECK FOR SAFETY GLASS AT TUB. 3. SAN-T IS REVERSED ON HORIZONTAL VENT. 4. NEED RIGHT/LEFT COUPLING, NOT A UNION 3/4 PIPE AT NORTHWALL. 5. FINISH ELECTRIC. 6. GAS TEST, SIZE OKAY. |
| 03/24/2000 |
FRAMING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |