Inspection History Details
Inspection Status: Approved
Inspection History: MEDICAL - GAS/TEST INTERMED
Permit Number - T99CM04875
Inspection Description - MEDICAL - GAS/TEST INTERMED
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/12/2000 | MEDICAL - GAS/TEST INTERMED | Approved | ||
05/25/2000 | MEDICAL - GAS/TEST INTERMED | Correction Required | ADDTL COMMS - ENGINER OF RECORD? 1. WHY WAS THIS NOT CALLED FOR PRIOR TO RESS. TEST? 2. VAC. LINE 60 PSI 3. NIT, NITOROUS OXIDE, OXYGEN 160 PSI COMPRESSER AIR, 4. DID NOT SEE CONTRACTOR INSTALLERS NITROGEN FLOW WHILE BRAZING, THIS CONTRACTOR NEEDS TOBE ADVISED OF PROPER PROCEDURE FOR MED GASES. 5. ADVISE THIRD PARTY CERTIFICATION CONTR AND WANT TO BE PRESENT WHEN CERTIFICATION PROCESS BEGINS. | |
05/25/2000 | MEDICAL - GAS/TEST INTERMED | Partial Approval | PARTIAL APPROVAL |