Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T99CM04875
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/08/2000 | ELECTRIC - ABOVE CEILING | Correction Required | ADDTL COMMS - OK STORE ROOM/OPERATING ROOM. | |
05/11/2000 | ELECTRIC - ABOVE CEILING | Correction Required | ADDTL COMMS - POWER AND BRANCH CIRCUITS/WIRING MUST BE INSTALLED USING APPROVED RACEWAY PER ART,517 N.E.C.-IN OR ROOM FLEX NOT ALLOWED MC CABLE ALLOWED ONLY IF LISTED FOR MEDICAL FACILITY USE J-BOXES MUST BE ACCESSABLE, ABOVE HARD CEILING. | |
05/11/2000 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0245* |