Permit: T99CM04875

Parcel: 13314227B


Addresses:

1400 N WILMOT RD

Inspection Status: Correction Required

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/08/2000 ELECTRIC - ABOVE CEILING Correction Required ADDTL COMMS - OK STORE ROOM/OPERATING ROOM.
05/11/2000 ELECTRIC - ABOVE CEILING Correction Required ADDTL COMMS - POWER AND BRANCH CIRCUITS/WIRING MUST BE INSTALLED USING APPROVED RACEWAY PER ART,517 N.E.C.-IN OR ROOM FLEX NOT ALLOWED MC CABLE ALLOWED ONLY IF LISTED FOR MEDICAL FACILITY USE J-BOXES MUST BE ACCESSABLE, ABOVE HARD CEILING.
05/11/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*