Inspection Status: Correction Required
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 06/08/2000 |
ELECTRIC - ABOVE CEILING |
|
Correction Required |
ADDTL COMMS - OK STORE ROOM/OPERATING ROOM. |
| 05/11/2000 |
ELECTRIC - ABOVE CEILING |
|
Correction Required |
ADDTL COMMS - POWER AND BRANCH CIRCUITS/WIRING MUST BE INSTALLED USING APPROVED RACEWAY PER ART,517 N.E.C.-IN OR ROOM FLEX NOT ALLOWED MC CABLE ALLOWED ONLY IF LISTED FOR MEDICAL FACILITY USE J-BOXES MUST BE ACCESSABLE, ABOVE HARD CEILING. |
| 05/11/2000 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0245* |