Permit: T99CM04850

Parcel: 13426001B


Addresses:

710 S KOLB RD 05

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/13/2001 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection 0000* NEED TO SEE SMOKE DETECTORS. INSTALL OUTSIDE AIR HOODS. LABEL UNITS.
12/19/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
NO COMBUSTIBLE ALLOWED IN A RETURN PLENUM RATED CEILING SPACE
OK TO INSULATE DUCT
OK TO PROCEED
SMOKE DETECTORS GO IN THE SUPPLY NOT THE RETURN AS PER 1994 UMC
10/27/2000 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
NEED ACCESS PANEL IN CEILING FOR MOTORIZED DAMPER ABOVE WOMEN'S RESTROOM. OK TO SHEET ROCK AFTER OPENING IS FRAMED
INSPECTION ON RESTROOMS ONLY