Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/13/2001 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection 0000* NEED TO SEE SMOKE DETECTORS. INSTALL OUTSIDE AIR HOODS. LABEL UNITS. | |
| 12/19/2000 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection 0000* NO COMBUSTIBLE ALLOWED IN A RETURN PLENUM RATED CEILING SPACE OK TO INSULATE DUCT OK TO PROCEED SMOKE DETECTORS GO IN THE SUPPLY NOT THE RETURN AS PER 1994 UMC |
|