Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/13/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* ALL CORRECTIONS HAVE BEEN MADE |
|
| 11/09/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* NEED TO REJECT COMPLETE ELECT. WIRING TO MAKE UP AIR (EVAP. CLR) ANCHOR MAKE UP AIR TO UNIT TO ANGLE BASE |
|
| 11/08/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* NOT READY |
|
| 11/06/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* LABEL EQUIPMENT ON ROOF HOOK UP LOW VOLTAGE TO A/C UNITS INSTALL FUSES IN DISCONNECTS MAKE UP AIR MUST BE MIN 10' AWAY FROM EXHAUST FANS ANCHOR CONDENSING UNITS BLOCK CONDENSATE DRAIN ON ROOF CORRECT AND RECALL FOR FINAL |