Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2000 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection 0000* ENGINEERS LETTER AND MURRAY INFO. PROVIDED |
|
| 10/26/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | GROUNDING CONNECTIONS 370-40P, 250-8 CANNOT BE MADE WITH SHEET METAL SCREWS GROUND DISCONNECT SWITCHES AT SERVICE CIRCUIT BREAKERS IN PANELS DO NOT COMPLY WITH PLANS MUST BE RATED 14 K AIC MIN |