Inspection Status: Correction Required
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 02/24/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. WASTE AND VENT SYSTEM OK 2. OVERHEAD WATER DISTRIBUTION OK 3. OK TO DRYWALL 4. ALL CORRECTIONS HAVE BEEN MADE |
| 02/17/2000 |
PLUMBING - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. ABS HORIZONTAL VENTS MUST HAVE A HANGER EVERY 4 2. URNIAL DRAIN CANNOT CONNECT TO C.O. TEE MUST BE A DRAINAGE FITTING BOTH URNIALS 3. OVERHEAD HORIZONTAL COPPPER MUST HAVE HANGERS EVERY 8 4. LOOSE COPPER WATER LINES BY WATER HTR |
| 02/17/2000 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0000* |