Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T99CM04670
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/21/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
02/14/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1) 5 TON CONDENSOR AT ENTRANCE STILL NOT FUSED CORRECTLY. 2) 2 CONDENSORS AT ENTRANCE NOT LABELED CORRECTLY. 3) CORRECTIONS ON WEST SIDE OF BLDG NOT COMPLETED | |
02/08/2001 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* CHECK ALL REF. LINES FOR CLEARANCE TO STEEL UNISTRUT NUMBER ALL DISCONNECTS W/PROPER CONDENSER NUMBERS DONOT LEAVE CONTROL WIRING EXPOSED TO ANY SUN |
|
02/05/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1) INSULATE REFRIGERATOR LINES 2) CANNOT HAVE LOW VOLTAGE WIRE EXPOSED. 3) CONDENSOR OVER FUSED 4) LABEL ALL EQUIPMENT AIR HANDLERS AND CONDENSORS. DO NOT USE INK OR OUTDOOR UNITS. 5) HOOK UP LOW VOLTAGE TO CONDENSORS 6) PAINT EXPOSED PVC WITH SYNTHETIC LATEX PAINT. 7) CHECK FOR HOSE CLAMPS ON 3/8 PLASTIC HOSE ON CONDENSATE DRAIN PIPES |