Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
Permit Number - T99CM04670
Inspection Description - PLUMBING - SEWER HCS CONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2000 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection 0000* P.O.C. OF NEW BLDG SEWER TO SEWER MAIN OK OK TO BACKFILL TRENCH |
|
09/23/2000 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection 0999* CAN NOT MAKE A HORIZONTAL TAP ON SEWER MAIN. VERTICAL OR 45 DEGREE ONLY A DIRECTIONAL FITTING IS REQUIRED FOR A HORIZONTAL CONNECTION MUST EXPOSE BLDG DRAIN TO BLDG SEWER CONNECTION |
|
09/19/2000 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection 0000* 1. SOIL WATER TEST OK 2. BLDG DRIAN IS STUBBED OUT OF BLDG WITH C.O. BLDG SEWER HAS NOT BEEN CONNECTED 3. SITE SEWER OK TO P.O.C. OF SEWER MAIN 4. MUST HAVE SURVEYOR TO CERTIFY VERIFICATION OF GRADE EVERY 50' PRIOR TO BACKFILL 5. OK TO BACKFILL TRENCH |