Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* SECURE M/C CABLE AS PER CODE CORD TO FIXTURE CON NOT PASS THRU STRUCTURAL CEILING 400-5 (2) |
|
| 10/12/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TEMP C OF O SUBJECT TO LETTER REGARDING BLACK ORDERED LIGHT FIXTURES BOND HAS BEGIN POSTED |
|
| 10/11/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* STRAP CONDUIT NEED FITTING ON END OF CONDUIT FOR TRANSITION FROM M/C TO CONDUIT ROOF LABEL DISCONNECTS IDENTIFY GROUNDING EQUIPMENT CONDUTOR SUPPORT CONDUIT CORRCTLY USING TEMP LIGHT WHERE AWAITING SHIPMENT |
|
| 10/05/2000 | ELECTRIC - FINAL | Not ready for Inspection | 10/05/00 NOT READY NO NOTES |