Inspection Status: Correction Required
Inspection History: MECHANICAL - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 05/31/2000 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - STILL NEED TO SEPERATE PRIMARY CONDENSATE DRAIN FROM SECONDARY. SECONDARY NEEDS TO BE RUN SO IT CAN BE READILY SEEN IF PRIMARY BECOMES BLOCKED. BOTH FLOWING INTO SOME LINE DOES NOT ALLOW THIS TO BE DETERMINED. LOOKS MUST BETTER. |
| 05/30/2000 |
MECHANICAL - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. NO APP. PLAN ON SITE 2. MINIMUM FLEX DUCT R-6 RATING NO 4.2 IN ATTIC SPACE 3. WHERE IS SKUTTLE ATTIC ACCESS TO AIR HANDLER? 4. NO PERMANENT LIGHT FIXTURE FOR SERVICE 5. PLAN TO PROVIDE CLEAR ACCESS TO FRONT OF AIR HANDLER SERVICE AREA |
| 05/30/2000 |
MECHANICAL - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000* |