Permit: T99CM04562

Parcel: 103182070

Inspection Status: Correction Required

Inspection History: FRAMING

Permit Number - T99CM04562

Inspection Description - FRAMING

Inspection Status - Correction Required

Date Description Inspector Results Comments
01/04/2000 FRAMING Correction Required ADDTL COMMS - 1. ITEMS 1, 5, 9, 10, 11 FROM 12/23/99 INSPECTIION NOT COMPLIED WITH. 2. LATH NOT COMPLETE AT POP OUTS OR NAILED UNDER BACK PORCH LEDGER.
01/04/2000 FRAMING Denied IVRS - Inspection 0999*
12/23/1999 FRAMING Correction Required ADDTL COMMS - 1. PROVIDE STT22S BOTH SIDES OF DOUBLE TOP PLATE AT KITCHEN SHEAR WALL. 2. NAIL GFCI OUTLET AT KITCHEN WALL. 3. KITCHEN EXHAUST HOOD DUCT NOT THROUGH ROOF. 4. PROVIDE SHIMS UNDER HEADERS NOT BEARING ON TRIMMERS AT BEARING WALLS. 5. PROVIDE 1/2 ANCHOR BOLTS AT ENTRY DOOR BOTH SIDES. 6. GROUT TUBS COMPLETELY. 7. LIGHT CAN OVER SINC - IS IT RATED TO BE IN CONTACT WITH ROFFING O.S.B. 8. SUPPORT 4 GANG BOX AT HALL BATH AND MASTER BATH. NOTE: THIS BOX MAY BE OVER LOADED. 9. MOVE ALL AQUA PEX MIN. 12 FROM ALL LIGHT CANS. 10.SECURE TUB DIVERTERS. 11.NAIL OFF FHA AT LAUNDRY DRYER DUCT. STOPPED INSPECTION.
12/23/1999 FRAMING Denied IVRS - Inspection 0999*