Inspection History Details
Inspection Status: Correction Required
Inspection History: FRAMING
Permit Number - T99CM04562
Inspection Description - FRAMING
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2000 | FRAMING | Correction Required | ADDTL COMMS - 1. ITEMS 1, 5, 9, 10, 11 FROM 12/23/99 INSPECTIION NOT COMPLIED WITH. 2. LATH NOT COMPLETE AT POP OUTS OR NAILED UNDER BACK PORCH LEDGER. | |
01/04/2000 | FRAMING | Denied | IVRS - Inspection 0999* | |
12/23/1999 | FRAMING | Correction Required | ADDTL COMMS - 1. PROVIDE STT22S BOTH SIDES OF DOUBLE TOP PLATE AT KITCHEN SHEAR WALL. 2. NAIL GFCI OUTLET AT KITCHEN WALL. 3. KITCHEN EXHAUST HOOD DUCT NOT THROUGH ROOF. 4. PROVIDE SHIMS UNDER HEADERS NOT BEARING ON TRIMMERS AT BEARING WALLS. 5. PROVIDE 1/2 ANCHOR BOLTS AT ENTRY DOOR BOTH SIDES. 6. GROUT TUBS COMPLETELY. 7. LIGHT CAN OVER SINC - IS IT RATED TO BE IN CONTACT WITH ROFFING O.S.B. 8. SUPPORT 4 GANG BOX AT HALL BATH AND MASTER BATH. NOTE: THIS BOX MAY BE OVER LOADED. 9. MOVE ALL AQUA PEX MIN. 12 FROM ALL LIGHT CANS. 10.SECURE TUB DIVERTERS. 11.NAIL OFF FHA AT LAUNDRY DRYER DUCT. STOPPED INSPECTION. | |
12/23/1999 | FRAMING | Denied | IVRS - Inspection 0999* |