Inspection Status: Correction Required
Inspection History: ELECTRIC - ABOVE CEILING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/14/2000 |
ELECTRIC - ABOVE CEILING |
|
Correction Required |
ADDTL COMMS - DENIED THERE IS NO SCREWS OR CLIPS ON REUSED FLUORESCENT FIXTURES LEAVE ALL OPEN AND RECALL |
| 02/14/2000 |
ELECTRIC - ABOVE CEILING |
|
Denied |
IVRS - Inspection 0999* |
| 12/28/1999 |
ELECTRIC - ABOVE CEILING |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 12/23/1999 |
ELECTRIC - ABOVE CEILING |
|
Correction Required |
ADDTL COMMS - -TAPPING OR OTHER MEANS OF SEPERATING THE COPPER LINER AWAY FROM M.C. CABLE IS NECESSARY. -FHA STRAPS REQUIRED AT VARIOUS LOCATIONS TO PROTECT MC CABLE WHERE CLOSER THAN 1 1/4 FOUR OF STUD. -PROPERLY STRAP M.C. CABLE AT REQUIRED INTERVOLS. -COMBINING OF A/C CIRCUIT WILL REQUIRE DERATING OF CONDUCTIVE AND CONDUIT FILL REQUIREMENTS. -COMBINING OF PANEL CIRCUIT WILL NEED DERATING AND APPROPRIATE ADJUSTMENTS IF ANY. -RE-TAG PROPER COLOR CODING FOR M.C. BRACE CIRCUITS. |
| 12/23/1999 |
ELECTRIC - ABOVE CEILING |
|
Denied |
DENIED |