Permit: T99CM04538

Parcel: 125020780


Addresses:

3025 E 2ND ST

Inspection Status: Correction Required

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/13/1999 ELECTRIC - INTERMEDIATE Correction Required ADDTL COMMS - 1. GROUND ALL METAL BOXES. 2. INSTALL ALL ELECT. PER PLAN. 3. ALL JUNCTION BOXES TO BE EXCCESSIBLE. 4. INSTALL APPROVED BOX FOR CEILING FAN. 5. #10-4 CIRCUIT FOR DRYER. 6. DRYER AND WASHER TO BE ON SEPERATE CIRCUITS. 7. REMOVE OLD WIRES. 8. COMPLETE NEW WIRES TO PANEL BOX.
08/13/1999 ELECTRIC - INTERMEDIATE Not ready for Inspection NOT READY FOR INSPECTION